Fuel Solenoid Valve – Normally Open (YKT A)
Fuel Solenoid Valve – Normally Open (YKT A) is a solenoid valve for controlling fuel flow in burners and liquid fuel lines.
Contents
Technical Specifications
| Function | 2/2-way, normally open (NO) |
|---|---|
| Size range | 3/8″ – 1″ |
| Connection | Threaded, BSP (NPT on request) |
| Body | MS 58 brass |
| Coil | IP65, class H, 100% ED |
| Diaphragm and seal options | NBR (-10/+80 °C), EPDM (-10/+130 °C), Viton (-10/+160 °C), PTFE (-10/+180 °C) |
Sizes and Codes
| Size range | Code | Datasheet |
|---|---|---|
| 3/8″ | YKTA1512 | |
| 1/2″ | YKTA1513 | |
| 3/4″ | YKTA1514 | |
| 1″ | YKTA1515 |
How Does It Work?
With the coil de-energised the valve is open and the medium flows freely. When the coil is energised the valve closes; when power is removed it opens again.
Applications
- Oil burners
- Fuel supply lines
- Generator and boiler fuel lines
Selection and Installation
Install the solenoid valve with the coil on top and fit a strainer upstream. For high temperatures, specify the diaphragm and seal material when ordering. Specify the coil voltage (AC/DC) when ordering. Send us your working pressure, temperature and application, and our technical team will recommend the right model and size.
Other function: Fuel Solenoid Valve – Normally Closed (YKT).
Download the datasheet for each size from the table above. Prices and online orders: Unox Online.
For solenoid valve types and selection, read our what is a solenoid valve guide; see all models on our solenoid valves page.