Blog
What Is an Actuator? Types, Working Principle and Selection
An actuator is the drive unit that moves a valve or damper using an energy source such as electricity or compressed air, instead of turning it by hand. It converts the signal from the control system into mechanical motion, so the valve can be opened and closed remotely, automatically and at the required speed. The two most common types in industrial plants are electric actuators and pneumatic actuators.
Contents
What Does an Actuator Do?
An actuator rotates or pushes the valve stem to open, close or regulate the flow. It is used on valves that are hard to reach, that operate frequently or that must work as part of an automation system. The valve shuts off the flow; the actuator is the part that moves the valve. A valve and actuator assembled together as a ready-to-use unit is called an actuated valve.
How Does an Actuator Work?
Every actuator converts an energy source into motion. The type of energy used determines the type of actuator.
How an Electric Actuator Works
The force produced by the electric motor is transmitted to the output shaft through a gear train inside the housing, and the shaft rotates. The gear train provides constant torque throughout opening and closing. At the end positions, limit switches stop the motor.
How a Pneumatic Actuator Works
Compressed air pushes the pistons inside the housing. The linear movement of the pistons is converted into rotary motion of the shaft by a rack and pinion, and the valve opens or closes.
Types of Actuators
Actuators are classified by the energy they use, the motion they produce and the way they are controlled.
Electric Actuator
Operates the valve with an electric motor. Because it needs no air line, it can be used wherever electricity is available. Unox electric actuators are available with 24 V DC and 24, 110, 220 and 380 V AC supply options. See our electric actuators page for details and our electric actuator guide for more information.
Pneumatic Actuator
Operates the valve with compressed air and opens or closes it within seconds. There are two types:
- Double acting: Opens the valve with air and closes it with air. If the air supply is lost, it stays where it is.
- Single acting (spring return): Moves the valve in one direction with air; when the air is cut off, springs return it to its starting position.
See our pneumatic actuators page and our pneumatic actuator guide for details.
By Motion: Quarter-Turn, Multi-Turn and Linear
- Quarter-turn (rotary) actuator: Rotates the shaft 90°. Used on ball and butterfly valves.
- Multi-turn actuator: Turns the shaft through many revolutions. Used on gate, knife gate, globe and diaphragm valves.
- Linear actuator: Pushes and pulls the stem in a straight line. At Unox, linear actuators are not sold separately; they are used on control valves.
By Control: On-Off and Modulating
An on-off actuator moves the valve only to the fully open or fully closed position. A modulating (proportional) actuator stops the valve at intermediate positions according to a control signal such as 4-20 mA, so the flow can be regulated.
Electric or Pneumatic?
| Electric actuator | Pneumatic actuator | |
|---|---|---|
| Energy source | Electricity | Compressed air |
| Operating time | 6–100 seconds depending on model | A few seconds |
| On loss of power | Stays in position; spring return models move to the safe position | Double acting stays in position; single acting returns to the safe position by spring |
| Modulating control | With 4-20 mA signal models | With a positioner |
| Preferred when | No air line is available | Compressed air is available; fast and frequent operation |
For a detailed comparison, see difference between electric and pneumatic actuators.
Unox Actuator Models
| Model | Series | Type | Torque / size |
|---|---|---|---|
| Rotary Electric Actuator | UKST | Quarter-turn, on-off | 15–2000 Nm |
| 4-20 mA Proportional Electric Actuator | UKST | Quarter-turn, modulating (4-20 mA) | 15–2000 Nm |
| Plastic Body Electric Actuator | URL | Quarter-turn, on-off | 30–50 Nm |
| Spring Return Electric Actuator | UKST.SR | Quarter-turn, spring return | 40–420 Nm |
| Multi-Turn On-Off Electric Actuator | AZ | Multi-turn, on-off | F10–F35 flange |
| Multi-Turn Proportional Electric Actuator | AZ | Multi-turn, modulating | F10–F35 flange |
| Ex-Proof Electric Actuator | E-UKST | Explosion-proof | — |
| Double Acting Pneumatic Actuator | UDA | Pneumatic, double acting | U40–U270 |
| Single Acting Pneumatic Actuator | USA | Pneumatic, single acting | U40–U270 |
| Low Temperature Pneumatic Actuator (-50 °C) | — | Pneumatic, low temperature | U40–U270 |
| 120° Rotation Pneumatic Actuator | — | Pneumatic, 120° rotation | U40–U270 |
| Ex-Proof Pneumatic Actuator | — | Pneumatic, explosion-proof | — |
How to Choose an Actuator
- Valve type and torque: Ball and butterfly valves need a quarter-turn actuator; gate and globe valves need a multi-turn actuator. The actuator torque must cover the torque the valve requires.
- Energy source: Choose pneumatic if compressed air is available, otherwise electric. Specify the supply voltage for electric actuators and the air pressure for pneumatic actuators.
- Control: On-off for open/close only; a modulating model to regulate flow.
- Fail-safe position: If the valve must open or close when power or air is lost, choose a spring return electric or a single acting pneumatic actuator.
- Ambient conditions: Use an ex-proof model in hazardous areas and the low temperature model in very cold environments.
- Mounting: The actuator mounting flange must match the valve. Unox quarter-turn actuators comply with the ISO 5211 mounting standard.
Send us your application details and our technical team will recommend the right model.
Actuator Failures and Maintenance
The most common problems are the actuator not fully opening or closing the valve, operating slowly or not moving at all. For causes and solutions, see our actuator failure guide.
Frequently Asked Questions
What does actuator mean?
An actuator is a drive unit that converts an energy source into mechanical motion. On valves, it allows the valve to be opened and closed by electricity or compressed air instead of by hand.
What is the difference between an actuator and an actuated valve?
The actuator is only the drive unit. An actuated valve is the valve and actuator assembled together and ready to use.
What is the difference between single acting and double acting actuators?
A double acting pneumatic actuator opens and closes the valve with air. A single acting actuator works with air in one direction and returns by spring force when the air is cut off, so it is used where a fail-safe position is required.
What is the difference between on-off and modulating actuators?
An on-off actuator moves the valve fully open or fully closed. A modulating actuator also stops the valve at intermediate positions according to the control signal, allowing the flow to be regulated.
What does fail-safe mean?
It means the valve automatically returns to a predefined safe position (fully open or fully closed) when power or air is lost. Spring return electric and single acting pneumatic actuators achieve this with spring force.
What is ISO 5211?
ISO 5211 is the standard that defines the flange and shaft dimensions used to mount quarter-turn actuators on valves. Actuators and valves that comply with it can be mounted directly on each other.