Spring Return Electric Actuated Butterfly Valve
The spring return electric actuated butterfly valve moves the valve to its safe position (open or closed) by spring force when power is cut. With Unox UKST.SR series actuators, spring torque from 40 Nm to 420 Nm can be selected; the return time is about 7 seconds.
Valve and Actuator
| Valve type | Butterfly valve |
|---|---|
| Actuator | UKST.SR series spring return electric actuator |
| Control | On-off |
Actuator Models and Torque Values
| Model | Spring end torque | Motor power | Running time | Return time |
|---|---|---|---|---|
| UKST.SR40 | 40 Nm | 23 W | 15 s | 7 s |
| UKST.SR90 | 90 Nm | 36 W | 15 s | 7 s |
| UKST.SR140 | 140 Nm | 90 W | 15 s | 7 s |
| UKST.SR300 | 300 Nm | 131 W | 15 s | 7 s |
| UKST.SR420 | 420 Nm | 150 W | 15 s | 7 s |
When the supply is cut, the actuator drives the valve to the preset safe position (open or closed) by spring force.
| Supply voltage | 24 V DC, 110–120 V AC, 220–240 V AC (50/60 Hz) |
|---|---|
| Rotation angle | 90° |
| Protection class | IP67 |
| Ambient temperature | -20 °C / +60 °C |
| Safety integrity level | SIL 2 |
How Does It Work?
In normal operation the electric motor opens or closes the valve and winds the spring inside the actuator. When power is cut, the spring returns the valve to its safe position within a few seconds, so the line is never left uncontrolled during a power failure.
Applications
- Applications where the line must move to a safe position during a power failure
- HVAC, heating and cooling systems
- Lines where process safety is critical
Selection
The right model is selected by considering the valve size, medium, operating pressure and temperature together with the torque required by the actuator, the supply voltage and the control method. Send us your application and our technical team will recommend the right valve–actuator combination.
For other models see our electric actuated valves category; if you only need an actuator, see the spring return electric actuator page; for types and the working principle, read our what is an actuated valve guide.